24V proportional regulator |
 |
DC output 0-10V or 10-0V |
 |
Temperature range 0/+40°C |
 |
Adjustable P-band |
 |
Setback temperature via external timer |
 |
Wall mounting |
|
|
| Product Range |
| Type |
Product |
EAN-Nr |
| EFRP-91 |
Regulator for wall mounting with built-in sensor |
5703502540856 |
| |
Accessories for EFRP-91 * |
|
| ETF-144/99 |
Universal sensor for floor and ceiling |
5703866101069 |
| ETF-944/99-H |
Room sensor for wall mounting |
5703502500379 |
| ETF-1144/99 |
Duct sensor with adjustable flange |
5703866100406 |
| |
*) Remove the jumper from its pins for connection of remote sensor. |
| |
|
| Function |
EFRP has a temperature range of 0/+40°C. It submits a 0-10V DC control signal in proportion to the temperature deviation. The proportional band is adjustable. The control signal is 10V when the sensor indicates a temperature which corresponds to the preset temperature -0.5 X P-band. When the sensor temperature corresponds to the preset temperature +0.5 X P-band, the control signal is 0V.
The control signal can be changed to 10-0V by means of jumpers inside. |
|
| Application |
| In systems with water-based heating/cooling surfaces EFRP is used for regulating a desired room temperature via the valve actuator. EFRP can also be used in combination with step controller ETT-6 for regulating modulated controlled electrical heating surfaces, air condensers, compressors or gas boilers. |
|
| Technical data |
|
| Supply voltage |
14-24V DC or 24V AC ±10% |
| Power consumption |
Max. 30 mA |
| Temperature range |
0/+40°C |
| DC-output |
Max. 2 mA, 0-10V DC (10-0V DC) |
| Regulating mode |
Proportional |
| P-band adjustable |
1-6°C |
| Setback temperature |
Adjustable 3-10°C |
| Ambient temperature |
-10/+50°C |
| Dimensions L x W x D |
84 x 84 x 27 mm |
| Housing |
IP 30 |
|
|
| Settings |
| Proportional band, Temperature setback, Room temperature, 0-10V - 10-0V (different connections).
|
| Proportional band |
| Setting is made on the potentiometer behind the front panel.
|
| Temperature setback |
| Setting is made on the potentiometer behind the front panel. Activation of setback temperature must be done via potential free contact in remote contact timer.
|
| Mounting |
| EFRP-91 is with built-in sensor and is mounted on the wall in the room, where the temperature should be controlled. By removing the factory-mounted jumper the remote sensor can be connected.
|
| Power supply |
| EFRP is power-supplied from a power controller type EFR or EFM or from a separate 24V AC power supply.
|
| Control signal |
| The control signal is connected to the 0-10V DC terminals on the power controller type EFR or EFM or damper/valve motor.
|
|
|
|
|
|
|